DI-8B38 Strain Gage Input ModulesWide (3kHz) and Narrow (3Hz) Bandwidth
LEARN MORE...
Datasheet (PDF)
Compatible Products
Compatible Products
Accessories
Accessories
Similar Products
Similar Products
Application Notes
Application Notes
|
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
DI-8B38 HighlightsDI-8B modules are an optimal solution for monitoring real-world process signals and providing high level signals to a data acquisition system. Each DI-8B38 module isolates, filters and amplifies a full-bridge strain gage input signal and provides an analog voltage output. The 8B38 can interface to tranducers with a nominal resistance of 100Ω to 10kΩ depending upon the model. Bridge excitation is provided from the module with a stable 10.00V or 3.33V source. Full scale sensitivities of 2mV/V and 3mV/V are offered as standard. Signal filtering is accomplished with a five-pole filter optimized for time and frequency response which provides 100dB per decade of normal-moderejection above the filter cutoff frequency. One pole of this filter is on the field side of the isolation barrier for anti-aliasing, and the other four are on the system side. A special input circuit on the DI-8B38 module provides protection against accidental connection of power-line voltages up to 240VAC. Clamp circuits on the I/O and power terminals protect against harmful transients. Isolation is provided by optical coupling to suppress transmission of common mode spikes or surges. The module is powered from +5VDC, ±5%. The modules are designed for installation in Class I, Division 2 hazardous locations and have a high level of immunity to environmental noise. |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||