Model DI-5B33-02

Isolated 1V RMS 5B-style Amplifier

$305 each
In
Stock
  • Interfaces RMS Voltage (1V)
  • Designed For Standard Operation With Frequencies of 45Hz to 1kHz (Extended Range to 20kHz)
  • Compatible With Standard Current and Potential Transformers
  • ±0.25% Factory Calibrated Accuracy (Accuracy Class 0.2)
  • 1500 VRMS Continuous Transformer Based Isolation
  • Input Overload Protected to 480V Max (Peak AC and DC) or 10A RMS Continuous
  • ANSI/IEEE C37.90.1-1989 Transient Protection
  • View Dimensions and pinout
Tweet this page Like this product on Facebook Share this page on LinkedIn Email this page
DI-5B DAQ Amplifiers
This amplifier module measures 0-1V RMS.This amplifier module has 45 Hz to 1 kHz bandwidth.This data acquisition system has a 30-day Money back guaranteeThis amplifier is manufactured in the United States of America

Description

Each DI-5B33 True RMS input module provides a single channel of AC input which is converted to its True RMS dc value, filtered, isolated, amplified, and converted to a standard voltage output (see block diagram).

The DI-5B modules are designed with a completely isolated computer side circuit which can be floated to ±50V from Power Common, pin 16. This complete isolation means that no connection is required between I/O Common and Power Common for proper operation of the output switch. If desired, the output switch can be turned on continuously by simply connecting pin 22, the Read-Enable pin to I/O Common, pin 19.

The field voltage input signal is processed through a preamplifier and RMS converter on the field side of the isolation barrier. The converted dc signal is then chopped by a proprietary chopper circuit and transferred across the transformer isolation barrier, suppressing transmission of common mode spikes and surges. The computer side circuitry reconstructs, filters and converts the signal to industry standard outputs. Modules are powered from +5VDC, ±5%.

Accessories

DI-5B01

16-Position Backplane

$ 409
16-channel backplane for 5B modules

Description

16-channel backplane for 5B modules. Each module has its own analog bus. For use with DI-5B Modules.

DI-5B03

1-Position Backplane

$ 55
Single-channel backplane for 5B modules

Description

Single-channel backplane. For use with DI-5B Modules.

DI-5B04

2-Position Backplane

$ 129
Dual-channel backplane for 5B modules

Description

Dual-channel backplane. For use with DI-5B Modules.

DI-5B05

8-Position Backplane

$ 305
Dual-channel backplane for 5B modules

Description

8-position analog I/O backplane, non-multiplexed. For use with DI-5B Modules.

DI-BEFE

Base Element

$ 10
Base element with snap foot

Description

Base element with snap foot required for use with models DI-5B03 and DI-5B04 Backplanes. For use with DI-5B Modules.

DI-5B-PS

Power Supply

$65.00
Power Supply

Description

5V DC Power Supply for use with both DI-5B and DI-8B Backplanes.

DI-XSE

Side Element

$ 5
Side element

Description

Side element required for use with models DI-5B03 and DI-5B04 Backplanes. For use with DI-5B Modules and Backplanes.

Specifications

Input
Signal Range: 0V to 1V RMS
Standard Frequency Range: 45Hz to 1000Hz
Extended Frequency Range: 1kHz to 20kHz
Impedance: 1MΩ ±1% shunted by 100pF
Coupling: AC
Protection:
(Module Rating Only)
Continuous: 480V (Peak AC & DC)
Transient: ANSI/IEEE C37.90.1-1989
Accuracy*
Sinusoid: 50/60Hz: ±0.25% Span
45Hz to 1kHz: ±0.25% Reading Additional Factor
1kHz to 20kHz: ±0.75% Reading Additional Factor
Non-Sinusoid: Crest Factor = 1 to 2: ±0.05% Reading Additional Error
Crest Factor = 2 to 3: ±0.15% Reading Additional Error
Crest Factor = 3 to 4: ±0.30% Reading Additional Error
Crest Factor = 4 to 5: ±0.40% Reading Additional Error
Vs. Temperature: ±100ppm/°C
Isolation
Input to Output, Input to Power: Continuous: 1500Vrms max
Transient: ANSI/IEEE C37.90.1-1989
Output to Power (Continuous): 50Vdc max
Output Enable Control
Selection Time: 6.0µS @ Cload = 0 to 2000pF
Voltage: Max Logic “0”: +0.8V
Min / Max Logic “1”: +2.4V / +36V
Current, “0,1”: 0.5µA
Other
Rejection (50-60Hz Common Mode): 100dB
Response Time (0 to 99%): <400ms
Loop Voltage: +14Vdc min, +48Vdc max
Load Resistance (maximum): (Loop Voltage -14) / (Loop Current)
Supply Voltage: +5VDC ±5%
Supply Current: 30mA
Supply Sensitivity: ±200µV/% RTI
Environmental: Operating Temperature: -40ºC to +85ºC
Storage Temperature: -40ºC to +85ºC
Relative Humidity: 0 to 90% Noncondensing
Mechanical Dimensions: 2.28" × 2.26" × 0.60"
(58mm × 57mm × 15mm)

* At standard 60Hz factory calibration. For 10 to 100% rated span. Add an additional 0.25% error for 0 to 10% Span measurements. Accuracy includes nonlinearity, hysteresis and repeatability but not source or external shunt inaccuracy (if used).